Copper THHN Wire & Cable

Copper THHN Wire & Cable

600 Volts. Copper Conductor. Thermoplastic Insulation/Nylon Sheath, Heat, Moisture, Gasoline and Oil Resistant II. All Sizes Rated Both THHN and either THWN (sizes 14, 12, and 10 AWG) or THWN-2 (sizes 8AWG and larger)

Feature :

• THHN or T90 Nylon- Dry locations not to exceed 90° C
• THWN-2- Wet or dry locations not to exceed 90° C or locations not to exceed 75° C when exposed to oil
• THWN- Wet locations not to exceed 75° C or dry locations not to exceed 90° C or locations not to exceed 75° C when exposed to oil
• TWN75- Wet locations not to exceed 75° C
• MTW- Wet locations or when exposed to oil at temperatures not to exceed 60° C or dry locations not to exceed 90° C (with ampacity limited to that for 75° C conductor temperature per NFPA 79)
• AWM- Dry locations not to exceed 105° C only when rated and used as appliance wiring material

Models :

Conductor

Insulation Thickness(mils)

Jacket Thickness(mils)

Nominal O.D.(mils)

Approx.NetWt.Per

1000(lbs.)

Allowable Ampacities+

Size(AWGor kcmil)

No.of strands

60℃

75℃

90℃

14*

1

15

4

102

15

15

15

15

12*

1

15

4

119

23

20

20

20

10*

1

20

4

150

36

30

30

30

14*

19

15

4

109

16

15

15

15

12*

19

15

4

128

24

20

20

20

10*

19

20

4

161

38

30

30

30

8

19

30

5

213

63

40

50

55

6

19

30

5

249

95

55

65

75

4

19

40

6

318

152

70

85

100

3

19

40

6

346

189

85

100

115

2

19

40

6

378

234

95

115

130

1

19

50

7

435

299

110

130

145

1/0

19

50

7

474

372

125

150

170

2/0

19

50

7

518

462

145

175

195

3/0

19

50

7

568

575

165

200

225

4/0

19

50

7

624

718

195

230

260

250

37

60

8

694

851

215

255

290

300

37

60

8

747

1012

240

285

320

350

37

60

8

797

1174

260

310

350

400

37

60

8

842

1334

280

335

380

500

37

60

8

926

1655

320

380

430

600

61

70

9

1024

1987

350

420

475

750

61

70

9

11262464

400

475

535

1000

6170

9

12753257

455

545

615


Standards :

• ASTM - B3, B8, and B787 (19 Wire Combination Unilay-Stranded)
• UL Standards 83, 758, 1063, and 1581
• CSA C22.2 No. 75, T90 Nylon/TWN75 Sizes through 1000 kcmil
• NOM-ANCE 90° C
• Federal Specification A-A-59544
• NEMA WC-70 (ICEA S-95-658) Construction Requirements
• CT Rated in Sizes 1/0 AWG and larger
• VW-1 - Sizes 14 through 1 AWG